Search Products

8723

22AWG 2-Pair Unshielded Audio, Control & Instrument Cable

  • 22 AWG stranded (7x30) tinned copper conductors
  • Polypropylene insulation, twisted pairs
  • individually Beldfoil® shielded (100% coverage)
  • 24 AWG stranded tinned copper drain wire
  • PVC jacket
  Specifications
CONDUCTOR
Number of Conductor 4
AWG 22
Stranding 7x30
Number of Pair 2
INSULATION
Material PP - Polypropylene
Nominal Wall Thickness 0.009 in
COLOR CHART
1 Red & Black
2 Green & White
INNER SHIELD MATERIAL
Type Tape
Material Aluminum Foil-Polyester Tape
Material Trade Name Beldfoil® (Z-Fold®-foil side out)
Coverage 100%
Drainwire Material TC - Tinned Copper
Drainwire AWG 24
Drainwire Construction n x D 7x32
OUTER SHIELD MATERIAL
Material Unshielded
OUTER JACKET MATERIAL
Material PVC - Polyvinyl Chloride
Nominal Diameter 0.16 in
Nominal Wall Thickness 0.02 in
CONDUCTOR DCR
Individual Pair Nominal Shield DCR 15 Ohm/1000ft
Nominal Conductor DCR 14.7 Ohm/1000ft
CAPACITANCE
Nom. Capacitance Conductor to Other Conductor to Shield 62 pF/ft
Nom. Capacitance Conductor to Conductor 33 pF/ft
INDUCTANCE
Nominal Inductance 0.17 μH/ft
IMPENDANCE
Nominal Characteristic Impedance 52 Ohm
HIGH FREQUENCY
Nominal Insertion Loss 10 dB/100m
DELAY
Nominal Velocity of Propagation (VP) 66%
CURRENT
Max. Recommended Current [A] Per conductor @ 25°C (10C temperature rise): 2.3 A
VOLTAGE
UL Voltage Rating 300 V RMS
TEMPERATURE RANGE
UL Temp Rating: 60°C
Operating Temp Range -20°C To +75°C
MECHANICAL CHARATERISTICS
Bulk Cable Weight 17 lbs/1000ft
Max Recommended Pulling Tension 42 lbs
Min Bend Radius/Minor Axis 1.75 in
STANDARDS
NEC Articles 800
NEC/(UL) Specification CM
CEC/C(UL) Specification: CM
CPR Euroclass Eca
FLAMMABILITY, LS0H, TOXICITY TESTING
UL Flammability UL1685 UL Loading
UL voltage rating 300 V RMS
PLENUM/NON-PLENUM
Plenum (Y/N) No
Plenum Number 82723, 87723, 88723
*Product design & specifications are subject to change without notice.