8761
22AWG 2-Conductor Shielded Electronic Cable
- 2 Conductor 22AWG (7x30) Tinned Copper
- PO Insulation
- Overall Beldfoil® Shield
- PVC Outer Jacket, CM
Specifications | |
CONDUCTOR | |
Number of Conductor | 2 |
AWG | 22 |
Stranding | 7x30 |
Number of Pair | 1 |
INSULATION | |
Material | PE - Polyethylene |
Nominal Wall Thickness | 0.017 in |
COLOR CHART | |
1 | Black & Red |
OUTER SHIELD MATERIAL | |
Type | Tape |
Material | Aluminum/Polyester |
Material Trade Name | Beldfoil® |
Coverage | 100% |
Drainwire Material | TC - Tinned Copper |
Drainwire AWG | 20 |
Drainwire Construction n x D | 7x30 |
OUTER JACKET MATERIAL | |
Material | PVC - Polyvinyl Chloride |
Nominal Diameter | 0.175 in |
Nominal Wall Thickness | 0.025 in |
CONDUCTOR DCR | |
Nominal Conductor DCR | 16 Ohm/1000ft |
CAPACITANCE | |
Nom. Capacitance Conductor to Conductor | 24 pF/ft |
Nom. Capacitance Conductor to Other Conductor to Shield | 47 pF/ft |
INDUCTANCE | |
Nominal Inductance | 0.2 μH/ft |
IMPENDANCE | |
Nominal Characteristic Impedance | 64 Ohm |
CURRENT | |
Element | 10C temperature rise |
Max. Recommended Current [A] | 2.9 Amps per conductor @ 25°C ambient |
VOLTAGE | |
UL Voltage Rating | 300 V RMS (UL AWM Style 2092 |
TEMPERATURE RANGE | |
UL Temp Rating | 60°C (UL AWM Style 2092) |
Operating Temp Range | -20°C To +60°C |
MECHANICAL CHARATERISTICS | |
Bulk Cable Weight | 16 lbs/1000ft |
Max Recommended Pulling Tension | 27 lbs |
Min Bend Radius/Minor Axis | 1.75 in |
STANDARDS | |
NEC Articles | 800 |
NEC/(UL) Specification | CM |
CEC/C(UL) Specification | CM |
UL AWM Style | UL Style 2092 (300 V 60°C) |
CPR Euroclass | Eca |
FLAMMABILITY, LS0H, TOXICITY TESTING | |
UL Flammability | UL1685 UL Loading |
CSA Flammability | FT1 |
UL voltage rating | 300 V RMS (UL AWM Style 2092) |
PLENUM/NON-PLENUM | |
Plenum (Y/N) | No |
Plenum Number | 88761, 87761, 82761 |